Technical data PVM 450-100 TT, CM, ET

Grid connection (AC)
Nominal power 100 kW
Nominal voltage 400 V 2)
Grid frequency 50 Hz, 60 Hz
Line fuse (400 V connection)/
maximum output current AC
160 A
Power factor lamda 0.999
THD < 3%
Generator connection (DC)
Peak power DC 114 kWp
Maximum input voltage DC

850 V

Maximum input current DC 250 A
MPP voltage 450 V to 850 V
MPP trackers 1
Efficiency TT CM ET
Maximum efficiency > 96% > 97% > 98% 3)
European refficiency > 95% > 96% > 97% 3)
Dimensions5 TT CM ET
Hight 4) 1800 mm 1800 mm 1800 mm
Width 1400 mm 1400 mm   800 mm
Depth   600 mm   600 mm   600 mm
Weight   900 kg   670 kg   510 kg

General data
Operating 0 °C to +40 °C
Protection class IP 42 5) ,non - condensing
Cooling concept Air cooled
Consumption (operation / night) < 1 % AC nominal power / 1.5 W

Features
DC overvoltage protection, DC main switch, AC short - circuit proofing
Ground fault monitoring resp. earth leakage circuit breaker
Touch screen display, data logger

Options
GPRS monitoring
AC overvoltage protection
Earthing of PV generator 6)
GPRS modem
PV plant monitoring, error messaging per e-mail or per text message
Service contract, extended warranty

1 Only for 480 V DC input voltage
2 Different voltages on request
3 Exclusive of transformer
4 Dimensinons plus base, standard: 200 mm
5 From 68 kW only with connected ventilation system - otherwise IP 00; different protection classes on request
6 Only for TT topology

International Exhibition and Conference for Renewable Energies

May 09-11, 2012 in Verona, Italy